Compliant with:
· ANSI/TIA-568-C.2 6A
· ISO/IEC 11801 Class Ea
Application:
· VolP · ISDN · Token · 100M TP-PDM
· Analong and Data Video
· TR-16 Active and Passive
· 155M/662m/1.2G ATM
· IEEE802.3:100Bease, 100Base-T, 1000Base-T,
10GBase-T
Reference Standards
· UL444 · UL1581 · UL1666 · IEC 60332-1
· IEC 60332-3-24 · EN50399
Testing Standards
· ISO/IEC11801 · ANSI/TIA-568-C.2 · IEC 61156-5
Physical Parameters:
Conductor | Solid Bare Copper, 24AWG |
Insulation Materials |
High Density Polyethylene & Skin-foam-skin Polythene |
Insulation Diameter | 1.12mm Nom. (solial insulation) 1.33mm Nom. (SFS insulation) |
Overall Shield | Aluminum Foiled |
Double Overall Shield | Aluminum Foiled+ Braiding |
Jacket Diameter | 7.1mm Nom. (U / UTP) 7.3mm Nom. (U / FTP) 7.5mm Nom. (F / FTP) 7.6mm Nom. (S/FTP) (7.5/16.0)mm Nom.(F/FTP duplex) (7.7/16.3)mm Nom.(S/FTP duplex) |
Jacket Material | PVC or LSZH or PE(depending on the jackets) Compliant with RoHS and REACH |
Operating Temperature | - 30 ℃ ~+50 ℃ (LSZH/PE) - 20 ℃ ~+50 ℃ (PVC) |
Electrical Parameters(20℃ ):
Transmission Delay Skew | 45ns / 100m |
Transmission Speed | 69% |
DC Conductor Resistance | 9.38 / 100m |
DC Conductor Resistance Unbalance | 5% |
Unbalance to Ground Capacitance | 330pf / 100m |